FILTRATION INC.

PROVIDING QUALITY FILTERS FOR A CLEAR SOLUTION!!
HOME
FEATURES

Variety of cartridge configurations to replace current industry standard coalescers

Available in open end style with flat gaskets

End caps of open end style coalescers are bonded with head plastisol adhesive

Open end series with O-ring seals

Thread base construction for quick installation and positive seal

Type and number of layers of fiberglass determines coalescing performance

FICC SERIES

TECHNICAL DATA

Suggested pH range 5 to 9

Flow direction is outside to inside

225 degree F maximum operating temperature

Different series for different efficiencies

25 micron typically used on diesel fuel or heating oils

5 micron typically used when more efficiency or tighter filtration is required

2 micron series are typically used for lighter hydrocarbons as jet fuel, kerosene, gasoline, or naptha

COALESCING CARTRIDGES

The primary purpose of a coalescing cartridge is to remove free water from a hydrocarbon stream.  Those provided by Filtration Inc. are interchangeable with coalescers manufactured by the major OEM companies such as Velcon, Peco, Banner/Parker, and Facet.  The common factor with the most popular part numbers is the 6" outer diameter and 3 1/2" inner diameter with cartridge lengths varying from 11" to 56". Dependent upon application and internal configuration of the filter/coalescer vessel, other sizes and configurations of coalescers are available for specific applications. For more information, click here.

FICCP SERIES
The "CP" Series coalescing cartridge is an enhanced version of the FICC series.  This series has a pleated cellulose pre-filter to remove solid contaminants from the hydrocarbon fluid.  The removal of solids prolongs the life of the dense fiberglass coalescing media resulting in extended service life thus reducing overall cost of filtration/separation.  The physical dimensions and configuration of this series are the same as the FICC series.  The are available in 1 micron particle retention for critical coalescing applications. For more information, click here.
Note: Our coalescers are recommended for industrial coalescing applications in refineries and other Non-API qualified applications.  Coalscers for API or aviation applications are to be addressed on a case by case basis.

 

 

5990 Griggs Rd. - Houston, Texas 77023

Phone: (713) 644-5712 - Toll Free: (888) 644-5712